Technical FAQs

Ask a Question

Ground Leakage current on ATV61 or ATV71

Issue: 
What is the Ground leakage current for SCF3 fault?

Product Line:
ALTIVAR 61, Altivar 71

Environment:
All

Cause:
Drive is tripping on SCF3 fault.

Resolution:
The threshold for a SCF3 fault (short-circuit to Ground) is 25% of drive nominal current. It is a hardware detection and it is not adjustable.
Was this helpful?
What can we do to improve the information ?