How to set an ATV61/71 drive for feedback (analog output) to show motor frequency?

Issue:
How to set an ATV61/71 drive for feedback to show motor frequency?

Product Line:
Altivar 61, Altivar 71

Environment:
All

Cause:
Feedback from drive

Resolution:
Go into 1.5 inputs and outputs menu.
Go into Analog output configuration.
Set analog output type to desired value.  Options include 0-10VDC, 0-20mA, or 4-20mA.
Set analog output assignment to motor frequency.
Set max freqency under 1.1 Simply start to 60 hz for 1 to 1 bias.