How to assign a logic input to external fault on the ATS48?

Issue: 
How to assign a logic input to external fault on the ATS48?
 
Product Line:
Altistart 48
 
Environment:
All Serial Numbers
 
Cause:
Logic input programming
 
Resolution:
To assign a logic input to external fault do the following:
From RDY
Press down to IO Menu   press enter
Press down to LIx (3 or 4) press enter
Press the down arrow to  LIE (external fault) press enter    
ESC back to RDY
 