What will cause an LRF fault on the ATS48 soft starters?

Issue:
What will cause an LRF fault on the ATS48 soft starters?

Product Line:
Altistart ATS48 soft starters

Environment:
All

Cause:
Locked motor rotor. 

Resolution:
Locked rotor in steady state
This fault is only active in steady state with soft starter bypass
contactor. It is detected if the current in a phase is greater than
or equal to 5 IN for more than 0.2 s.
Check the mechanism for wear, mechanical play, lubrication, blockages,
 