What are the maximum number of auxiliary contacts that can be added to 8536/8502 Starter/Contactor

Issue:
What are the maximum number of auxiliary contacts that can be added to 8536/8502 Starter/Contactor

Product Line:
NEMA Contactors and Starters - GIC Product

Environment:
US Product

Cause:
Product Specifications

Resolution:
The maximum number of aux contacts listed are in addition to the supplied internal holding contact

Size 00 Max three poles - 4 single circuit auxiliary contacts (NO or NC) if second internal auxiliary contact is not used
Size 0-2 Max three poles - 4 single circuit auxiliary contacts (NO or NC)*
Size 0-2 Max three poles - 2 single circuit auxiliary contacts (NO or NC) plus one power pole adder
Size 0-2 four or five poles - 2 single circuit auxiliary contacts (NO or NC)
Size 3-4 two to five poles - 3 single circuit auxiliary contacts (NO or NC)
Size 5 two or three poles - 2 single circuit auxiliary contacts (NO or NC) plus one power pole adder
Size 6-7 two or three poles - 3 single circuit auxiliary contacts (NO or NC)
Size 6-7 two or three poles - 2 single circuit auxiliary contacts (NO or NC) plus one power pole adder

*when adding 4 external auxiliary contacts to one size 0 or 1 contactor, remove one of the return springs

See part number table below for selection: 
 
For Use With Kit description Ordering Information
 Type NEMA Size Class 9999
Type
External - Field Convertible
SA-SJ 00-7 1 N.O. contact SX6
1 N.C. contact SX7
1 N.O. and 1 N.C. isolated contacts SX8
1 N.O. overlapping contact SX9 *
1 N.C. overlapping contact  SX10 * 
External - Non-Convertible 
SA-SJ 00-7 1 N.O. Contact SX13
1 N.C. Contact SX14
1 N.O. and 1 N.C. isolated contacts SX15
1 N.O. overlapping contact SX16 * 
1 N.C. overlapping contact  SX17 *
Internal - Non-Convertible
SA-SD 00-2 1 N.O. Contact SX11 #
1 N.C. Contact SX12 #

* - Types SX9 and SX10 or types SX16 and SX17 must be used together and mounted on the same side of the contactor. They are suitable for applications where it is necessary for a normally open contact to overlap a normally closed contact. 
# - Types SX11 and SX12 are not for use on NEMA size 3 or larger. Internal contacts can also be used on Class 2510 types M and T manual starters 