Technical FAQs

Ask a Question

Video: Why does the Local/Remote button not work on the Process drive keypad?

Issue:
Why does the Local/Remote button not work on the Process drive keypad?

Product line:
Altivar 600, ATV630, ATV650, ATV930

Environment:
All

Cause:
Default programming

Resolution:
The factory settings for the Process drive is that the Local/Remote button is disabled.
To activate it, go to Complete Settings (CSt-) > Command and Reference (CrP) > HMI cmd. (bMP) and change it from Disabled (diS) to Bumpless (buMP).

Was this helpful?
What can we do to improve the information ?