ATV61: Why can the Forced Local parameter not be change from NO?

Issue:
Customer wants to use Forced Local but the drive will not allow the change.

Product line:
ATV61, ATV71, Altivar 61, Altivar 71

Environment:
all

Cause:
Incompatible functions

Resolution:
Forced local is not compatible with the Profile set to IO.  To use the Forced Local function, the Profile needs to be set to Separate or Not Separate. 

 