What wire sizes will fit into the QONK1, 2, 3, or 4 neutral bars?

Issue:
What wire sizes will fit into the neutral bars

Product Line:
QO Loadcentres

Environment:
Loadcentres

Cause:
Wire size guideline

Resolution: 
The QONK1, 2, 3, or 4 will accomodate wire sizes of #4 to #14 Cu, or #4 to #12 Al.
These neutral bars have a 90C rating.
Wire Size by Type and Torques
CU Wire Range AL Wire Range Torque (in-lbs)
#14 (2 wires) #12 (2 wires) 20-35
#12 (2 wires) #10 (2 wires) 20-35
#10 (2 wires) #10 (1 wire) & 
#12 (1 wire) (Solid or Stranded)
20-35
#12 (1 wire) & 
#14 (1 wire) (Solid or Stranded)*
  20-35
#10 (1 wire) & 
#14 (1 wire) (Solid or Stranded)*
  20-35
#10 (1 wire) & 
#12 (1 wire) (Solid or Stranded)*
  20-35
#10-14 (1 wire) #10-12 (1 wire) 20
#8 (1 wire) #8 (1 wire) 25
#4-6 (1 wire) #4-6 (1 wire) 35
*(Wire of same type )

Installation instructions are attached.
Load Centre box label has specific allowances.