What faults can be reset with ATV61 or ATV71 automatic restart function turned on?

Issue:
What faults can be reset with ATV61 or ATV71 automatic restart function turned on?

Product Line:
Variable Frequency Drives

Environment:
Applies to Altivar 61/71

Cause:
Customer wants to know if he can automatically restart the drive after an input phase loss fault 

Resolution:

Faults that can be reset with automatic restart function, after the cause has disappeared:
APF, CnF, COF, EPF1, EPF2, FCF2, Fd1, LFF2, LFF3, LFF4, nFF, ObF, OHF, OLC, OLF, OPF1, OPF2, OSF, OtF1, OtF2, OtFL, PHF, PtF1, PtF2, PtFL, SLF1, SLF2, SLF3, SPIF, SSF, tJF and ULF

NOTE: The drive must be set up for 2 wire control, be controlled by the terminal strip, and the run command must be maintained in order for the Automatic Restart function to attempt a restart.  Also, the cause of the original fault must be gone,

 