Issue:
How do I access the Comm Scanner Input and Output tables on the Altivar Process Drive?

Product Line:
Altivar Process Drive

Environment:
All serial numbers for Altivar Process Drive

Cause:
To configure the Comm. Scanner (Input/Output) tables:

Resolution:
Programming from the Drive:

[Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner
input]
  • Up to 8 input registers can be configured
  • By default the first 2 registers are pre-configured
    • [Scan. IN1 address] nMA1 - 3201 (EtA Status word)
    • [Scan. IN2 address] nMA2 - 8604 (rFrd - Output frequency)

[Communication] [Comm parameters] [Modbus SL] [Modbus Fieldbus] [Com. scanner
output]
  • Up to 8 output registers can be configured
  • By default the first 2 registers are pre-configured
    • [Scan.Out1 address] nCA1 - 8501(CMd word)
    • [Scan.Out2 address] nCA2 - 8602(LFrd - Output freq in rpm)

Programming from Somove:
[Parameter List] [Fieldbus] [Port - Modbus Serial] [Modbus Fieldbus] [Modbus SL] [Modbus Fieldbus] 

 