ATV212- customer wants to monitor the fan so it will set an alarm in their Modbus register to let them know the fan is not running, before the drive faults

Issue:
ATV212-customer wants to monitor the fan so it will set an alarm in their Modbus register to let them know the fan is not running, before the drive faults
 
Product Line:
 ATV212

Environment:
Modbus
 
Cause:
n/a
 
Resolution:
There is a Flashing L in the drive. This is to let you know you are getting close to a overheating fault. You can monitor this parameter ( FC91- register 64,657, bit 3 is the motor overload alarm).