Is it ok for a GFI Ground Fault Receptacle to be used downstream of a CAFI/AFI Arc-Fault Circuit Breaker?

Issue:
Is it ok for a GFI Ground Fault Receptacle to be used downstream of a CAFI/AFI Arc-Fault Circuit Breaker? Will they interfere with each other?

Product Line:
Circuit Breakers

Environment:
Applies to QO/QOB/HOM breakers with CAFI or AFI suffix
Applies to GFI Ground Fault Receptacles

Cause:
There is concern that the Arc-Fault Breaker and the Ground Fault Receptacle will interfere with each other's operation.

Resolution:
Yes, it is ok for a GFI Receptacle to be used downstream of a CAFI/AFI Arc-Fault Circuit Breaker. One does not interfere with the operation of the other.
NOTE: Depending on the situation, we suggest considering use of the DF Dual Function circuit breaker. This breaker combines CAFI Arc-Fault Protection with GFI Ground Fault Protection, all in one breaker. This would eliminate the need for a downstream GFI receptacle. Example catalog numbers are HOM115DF, QO120DF. For additional information on the Dual Function breaker, click this link, and use the search box to find additional information by using the words "Dual Function".