What is the consumption of the control coil for 8502 SF contactor?

1185 VA inrush and 85 VA sealed for 60 hertz or 1260 VA inrush and 89 VA sealed for 50 hertz. This also applies to all 8536 SF, 8538 SF, 8539 SF, 8606 SF, 8630 SF, 8640 SF, 8702 SF, 8736 SF, 8738 SF, 8739 SF, 8810 SF, 8903 SV, 8910 SYD230, 8940 S Size 4 except ``NP, 8941 NF, and 8941 CF devices.




CTA-ID : 4698