What is the operating voltage tolerance, catalog numbers, and clearing times for the Masterpact NT and NW shunt trip and shunt close coils?

Issue:  
What is the operating voltage tolerance, catalog numbers, and clearing times for the Masterpact NT and NW shunt trip and shunt close coils?

Product Line:
Masterpact NT NW

Resolution:
Shunt trip:  operating threshold is 0.7 to 1.1 Vn (nominal voltage)
Shunt close:  operating threshold is 0.85 to 1.1 Vn
Catalog numbers are the same for MX and MN (shunt trip and shunt close) devices; function is determined by placement in the breaker.
 
Voltage 50/60 Hz  T-, W-, & Y-Frame Fixed  T-Frame Drawout  W- & Y-Frame Drawout 
12 dc  S47359  S33809  S48490 
24–30 ac/dc  S47360  S33810  S48491 
48–60 ac/dc  S47361  S33811  S48492 
100–130 ac/dc  S47362  S33812  S48493 
200–240 ac/dc  S47363  S33813  S48494 
277 ac  S47364  S33814  S48495 
380–480 ac  S47365  S33815  S48496 

MX operating time at Vn:  50 ms ±10 (NW and NT)
XF operating time at Vn:  
70 ms ±10 (NW ≤ 4000 A)
80 ms ±10 (NW > 4000 A)
55 ms (NT)

NOTE:  Shunt trip (MX) and shunt close (XF) circuits must be energized for minimum of 200 ms.