What is the replacement coil for the electrically held 8903L lighting contactor?

Issue:
What is the part number for the replacement coil in an 8903 Type L contactor: 

Product Line:
 8903 type L Lighting contactors

Environment:
North American Products

Cause: 
Maintenance 

Resolution:
This depends on pole quantity and voltage: 2-6 poles, 9998L23 for 60hz or 9998L24 for 50hz. 7-12 poles, 9998LH23 for 60hz or 9998LH24 for 50hz.
 
 Poles  Coil Class and Type  HZ  Suffix Number
(complete coil number consists of the class and type followed by the suffix) 
Coil VA
 24v   110-115v   120v   208v   220v   240v   277v   380v   440v   480v   550v   600v   Inrush   Sealed 
2-6 9998L  60  23 - 44 50 [*] 53 55 - - 62 - 65 150 30
50 24 44 45 52 53 54 - 60 62 63 65 66 140 30
8-12  9998LH  60 23 - 44 50 [*] 53 55 - - 62 - 65 180 35
50 24 44 45 - 53 54 - 60 62 - 65 - 170 35

* - use a 60 Hz coil of the next higher voltage