Customer is experiencing nuisance tripping of circuit breakers in new motor control center buckets with circuit breaker combination starters.

Advised customer that the circuit breaker ships from the factory with the magnetic trip adjustment set at the minimum. This may need to be adjusted upwards in order to allow the cirucit breaker to hold and not trip during motor start.