Technical FAQs

Ask a Question

Does a QO250GFI require a load neutral connection?

Product Line:
Circuit Breakers

Environment:
Applies to QO-GFI, 50A and below

Resolution:
A load neutral connection is required only if there is a load neutral. The circuit breaker will perform properly without a load neutral on a 2-wire 240Vac circuit. However the neutral pigtail still has to be connected to panel neutral bar.

For more information on wiring please see instruction bulletin 48840-435-03 in our technical library.

Technical library:
http://products.schneider-electric.us/technical-library/



CTA-ID : 1876
Was this helpful?
What can we do to improve the information ?