Technical FAQs

Ask a Question

Is replacement coil available for 8911DPSG22V02?

Issue:
Are replacement coils available for the 8911DPSG22V02?

Product Line:
Nema Definite Purpose Contactos

Environment:
Maintenance

Cause:
Coil Replacement

Resolution:
Coil part number 9998DA1V02, coil consumption is 56 VA inrush and 6 VA sealed. However, this was the coil for the Series A or B DP contactor and is now obsolete with 
no replacement.  The contactor itself must be replace.  Series C coils will not fit the Series A or B contactor. 



CTA-ID : 10399
Was this helpful?
What can we do to improve the information ?