What is the accuracy rating of the metering CT's for Masterpact NW breakers? certified for revenue accuracy metering per ANSI C12.16?

Issue:
What is the accuracy rating of the metering CT's for Masterpact NW breakers? Are they certified for revenue accuracy metering per ANSI C12.16?

Product Line:
Masterpact

Resolution:
The CT`s were designed for C37.20.1 metering accuracy, not revenue accuracy.
Metering current transformers are optional and are mounted on the NW UL or ANSI cradle.
All metering transformers are accurate with the 0.3% accuracy class, 5 A output ratio at full load (for example, a 1600 A metering CT would send 5 A at the full load of 1600 A). 
A standard wiring harness is also included for factory-installed MCTs. Not available for neutral pole on a 4-pole circuit breaker. 
 