What Retaining Kit is required for back feeding a 2 pole branch circuit breaker in a Homeline load center, series S01, S02, S03, or S04?

Issue:
Selection

Product Line:
Load Center

Environment:
Retaining Kit

Cause:
Selection

Resolution:
HOM1RK secures one 2 pole branch circuit breaker when used as a back-fed main for HOM612L100F, HOM612L100S, HOM612L100RB, HOM48L125GC and HOM48L125GRB.
  *** NOTE: HOM612L100F, S or RB restricted to 100A back-fed main breaker. HOM48L125GC, RB restricted to 125A back-fed main.
HOM4RK2LA secures one 2 pole branch circuit breaker to the right side of the interior when used as a back-fed main for 125A convertible main load centers, Series S01, S02, S03, or S04.
  *** NOTE: Restricted to 125A back-fed main breaker.
HOM4RK2HA secures one 2 pole branch circuit breaker to the right side of the interior when used as a back-fed main for 150A - 225A convertible main load centers, Series S01, S02, S03, or S04.
   ***NOTE: Restricted to 125A back-fed main breaker.
HOM5RK secures one 2 pole, 150A - 200A branch circuit breaker when used as a back-fed main for 150A - 225A convertible main load centers, Series S01, S02, S03, or S04. 
   ***NOTE: The back-fed main breaker amperage cannot exceed the amperage rating of the load center.
   ***NOTE: The 150A - 200A branch circuit breakers require 4 spaces to mount on the load center interior.