Masterpact NW with Micrologic 6.0A trip unit and is doing primary injection testing on it. Asking if he can disable ground fault in order to perform testing.

Issue:  
Is there a way to defeat or disable ground fault on a Masterpact NW breaker for primary injection testing?  

Product line:  
Power circuit breakers

Environment:  
Masterpact NW circuit breakers with Micrologic trip units

Resolution:  
There are two ways to defeat ground fault on the NW breaker.  You can use the Hand Held Test Kit, Cat. No. S33594, or the Full Function Test Kit, Cat. No. S33595 OR you can use the looping method to counter the single phase current during primary injection testing.  See the attached Data Bulletin 0600DB9901 page 35, for looping method, or FAQ FA265488.