Technical FAQs

Ask a Question

What is the locked rotor current rating of the LC1K12 or LP1K12 contactors?

Product Line:
 
Tesys K Line Contactors
 
Resolution:
 
Locked Rotor ratings apply to devices tested and offered for definite purpose controls. The IEC products are tested to IEC Standards and carry short time ratings. The following are the permissible short time rating from cold start:
For 1 second, 115 amps.
For 5 seconds, 105 amps.
For 10 seconds, 100 amps.
For 30 seconds, 75 amps.
For 1 minute, 55 amps.
For 3 minutes, 50 amps.
For 15 minutes and greater, 25 amps.


CTA-ID : 2002470
Was this helpful?
What can we do to improve the information ?