Can you disable the Instantaneous function on Powerpact P, R and Masterpact?

Issue:
Can you disable the Instantaneous function on Powerpact P, R and Masterpact?

Product Line:
Powerpact P, R frame,  Masterpact NT, NW

Environment:

Cause:

Resolution:
The instantaneous setting can be turned OFF if the breaker has the Short Time function (5.0 or 6.0 trip unit). BUT, there is an instantaneous override function which will trip the breaker instantaneously on a high-level fault. See catalog for override values.