Can the QO Generator panels CQO48M30DSGP and CQO48M60DSGP be used with generators that have a bonded neutral?

Issue:
Application

Product Line:
Canadian Generator Panel

Cause:
Application

Resolution:
NO, These load center Generator Panels can ONLY be used with unbonded generators since they do not switch the neurtal, which is a code requirement in Canada.
NOTE: The load centers will have a label on them that will state "Suitable for use ONLY with generators which have an UNBONDED NEUTRAL". 


 