Technical FAQs

Ask a Question

What is the catalog number for the closing plate to cover the rectangular opening in an NQMB2Q main breaker adapter kit when it is used WITHOUT a main breaker?

Issue:
What is the catalog number for the closing plate to cover the rectangular opening in an NQMB2Q main breaker adapter kit when it is used WITHOUT a main breaker?

Product Line:
NQ Panelboard

Environment:
Maintenance

Cause:
Application change

Resolution:
The catalog numbers are: quantity of (1) 80110-320-02 closing plate, and quantity of (4) 80025-067-01 mounting screws.
If a customer has an NQ main breaker interior in the field which contains the Q frame breaker, and wishes to convert it to a MLO interior, they must remove the NQMB2Q main breraker kit and replace it with the NQ12RDE kit.  The interior already has line lugs so no additional lug kit would be required.
Any other NQ main breaker interior would require the removal of the main breaker kit, installation of an NQ12RDE kit and the installation of a lug kit as well.




 
Was this helpful?
What can we do to improve the information ?