Video: What are the restrictions to mounting QOB3110VH and larger branch breakers in a NQ panelboard?

Issue:
How does one mount QOB3110VH and larger branch breakers in a NQ panelboard?

Product Line:
NQ Panelboards

Environment:
NQ Panelboards sold in North America

Resolution:
The QOB3110VH through QOB3150VH requires 6 vertical spaces and the largest branch breaker which can be mounted adjacent to (across from) it is 40A.