Can you operate an ATV212 S-Flex with damper while you are in forced local mode (keypad)?

Issue:
Can you operate an ATV212 S-Flex with damper while you are in forced local mode (keypad)?

Product Line:
ALTIVAR 212 S-Flex

Environment:
All

Cause:
Damper control

Resolution:
No.  Terminals 5 and 6 will still need to be closed in order for the damper switch to be made and for the damper to activate before a command can be given through local control.