Do the Powerpact H, J, and L breaker work with the AMS and/or ERMS Arc Fault Reduction System?

Product Line:
Powerpact L

Resolution:
The Powerpact L breaker with 6.3A 6.3E 5.3A and 5.3E trip units will function with the AMS system.
Powerpact H and J breakers will not because they cannot accept a ZSI restraint signal.
They will NOT work with the ERMS arc-flash reduction system.