Technical FAQs

Ask a Question

How do you set up fault reset over the network with the ATV630 drives embedded Ethernet in I/O profile mode?

Issue:
How do you set up fault reset over the network with the ATV630 drives embedded Ethernet in I/O profile mode?

Product Line:
ATV630 or ATV930 in I/O Profile mode only

Environment:
All 

Cause:
Wants to reset the faults over Ethernet using Bit 1 of the command word CMD.

Resolution:
With Profile set to I/O the assignment for fault reset will be C501 as fault reset being Bit 1 of the CMD with embedded Ethernet and I/O profile.
C501 means Bit 1 of the CMD 8501 will allow the faults to be reset over the embedded Ethernet network.  