How to program an ATV630 to follow AI3 analog input for mA or DC signal?

Issue:
How to program an ATV630 to follow AI3 analog input for mA or DC signal?

Product Line:
Altivar 630, process

Environment:
All

Cause:
Programming, installation

Resolution:
AI3 can be configured for both DC scale or mA.
To perform this go into Complete Settings, Inputs/outputs, and AI/AQ tab, AI3 configuration.
Set AI3 type according (DC, mA, PTC man, Kty, Pt1000, etc.)
Set AI3 min type as 4 mA if needed.
Set AI3 max value as needed.

To allow the drive to look at AI3 as a speed refererence:

Go into Complete settings, Command and Reference, assign Reg Freq 1 Config AI3.

 