How can I monitor the Reference and Output Frequency on the ATV312 drive?

 Issue:
Customer is using the dial for speed control and not sure what speed the drive is running at.  He needs to check the output speed and reference speeds. 

Product line:
Altivar 312

Environment:
n/a

Cause:
Troubleshooting

Resolution:
While running the drive in Remote mode (no LED's flashing), Push the enter button, the dial, and turn to the SUP- menu.  Push Enter and dial to FrH.  FrH is the Reference Frequency.  How fast the drive is being told to run. 

Next, scroll down under the SUP- menu to rFr.  rFr is the output frequency, the speed at which the motor should be running. 

Note:  Depending on the ACC and DEC times, the drive may take some time to change the speed value.