Technical FAQs

Ask a Question

What type of Surge Protection Device modules are used in the Model 6 Low Voltage Motor Control Center

The Surgelogic SPD utilized in the M6 LVMCC uses the EMA series modules. The replacement modules can be ordered via the part numbers listed in the Digest 177 Page 6-3 Table 6:2 (EMA Replacement Modules). Most commonly used modules for M6 LVMCCs are 208/120, 480/277 & 600/347 Vac 4-Wire Wye Systems. The same module is used for 3-Wire Solidly Grounded Wye systems. Refer to the electrical control schematics in the MCC drawing package for instructions regarding the Neutral termination on the SPD.
Note: Ensure the MCC drawings are referenced for proper selection of the System Voltage and the Peak Surge Current rating to match the existing modules. If in question, please contact a local Schneider Electric authorized distributor or Schneider Electric Customer Care Center.
You may find several useful documents to include: Document number 8222-0010 Modular SPD Replacement Instructions
Schneider Electric USA website link:
https://www.schneider-electric.us/en/?mrkgcl=986&mrkgadid=3138316287&utm_campaign=US%2520-%2520Always%2520On%2520(Brand)&utm_source=google&utm_tactic=Schneider%2520Electric%2520Brand%2520Broad&utm_term=schneider%2520electric&adpos=1t1&creative=251712253102&device=c&matchtype=b&network=g&gclid=EAIaIQobChMIq7TG46WJ3wIV2UwNCh2MbwiPEAAYASAAEgL70vD_BwE#xtor=SEC-412-GOO-[23017976817]-[251712253102]-S-[%2Bschneider%20%2Belectric]
 
Was this helpful?
What can we do to improve the information ?