Does the Inhibit Thermal Imaging feature of either the Full Function Test Kit (FFTK) or Hand Held Test Kit (HHTK) supported in all trip units?

Issue:
Can the FFTK or HHTK inhibit thermal imaging? 

Product Line:
Molded Case Circuit Breaker Trip Unit Accessory

Environment:
Micrologic Trip Unit Accessory

Cause:
Application of test kits

Resolution:
The Handheld Test Kit (S33594) and the Full Function Test Kit (S33595) can NOT inhibit thermal imaging on standard trip units (2.0, 3.0 and 5.0).  It is designed for the ``A``, ``P`` and ``H`` trip units.

Note: For non-communicating Micrologic, ET and STR trip units a 15-minute delay must be observed to allow reset of thermal memory.