TeSys GV7 Manual Starter and Protector, thermal magnetic circuit protector, rocker lever, 3 P, AC-3, 90...150 A, high interrupt

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range
    TeSys
    product name
    TeSys GV7
    device short name
    GV7R
    device application
    Motor
    poles description
    3P
    network type
    AC
    utilisation category
    AC-3 conforming to IEC 60947-4-1
    network frequency
    50/60 Hz conforming to IEC 60947-4-1
    breaking capacity
    50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    [Ics] rated service short-circuit breaking capacity
    100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
    100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
    thermal protection adjustment range
    90...150 A
    trip unit technology
    Thermal-magnetic
    Complementary
    mounting mode
    By screws
    By clips
    mounting support
    Panel mounting
    Rail
    Kit for fixing the switchgear
    Flush
    mounting position
    Vertical
    motor power kW
    110 kW at 660...690 V AC 50/60 Hz
    55 kW at 400...415 V AC 50/60 Hz
    75 kW at 400...415 V AC 50/60 Hz
    75 kW at 500 V AC 50/60 Hz
    90 kW at 500 V AC 50/60 Hz
    90 kW at 660...690 V AC 50/60 Hz
    control type
    Rocker lever
    System Voltage
    690 V AC 50/60 Hz conforming to IEC 60947-2
    [Ui] rated insulation voltage
    750 V AC 50/60 Hz conforming to IEC 60947-2
    [Ith] conventional free air thermal current
    150 A conforming to IEC 60947-4-1
    [Uimp] rated impulse withstand voltage
    8 kV conforming to IEC 60947-2
    power dissipation per pole
    8.7 W
    power dissipation per pole
    8.7 W
    mechanical durability
    40000 cycles
    electrical durability
    40000 cycles AC-3 at 440 V In/2
    20000 cycles AC-3 at 440 V In
    operating rate
    25 cyc/h
    rated duty
    Continuous conforming to IEC 60947-4-1
    connection pitch
    1.38 in (35 mm) without spreaders
    1.77 in (45 mm) with spreaders
    connections - terminals
    Bars
    Cable with lug - external diameter : 10 mm
    Bare cable connectors 1.5...95 mm²
    Screw
    tightening torque
    10 N.m - on screw - screw M6
    15 N.m - on bare cable connectors- cable 1.5...95 mm²
    mechanical robustness
    Shocks 15 Gn for 11 ms conforming to IEC 60068-2-27
    Vibrations 2.5 Gn, 0...25 Hz conforming to IEC 60068-2-6
    suitability for isolation
    Yes conforming to IEC 60947-1
    phase failure sensitivity
    Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
    height
    4.92 in (125 mm)
    width
    4.13 in (105 mm)
    depth
    4.37 in (111 mm)
    product weight
    4.45 lb(US) (2.02 kg)
    Environment
    standards
    EN/IEC 60947-4-1
    NF C 63-120
    VDE 0660
    VDE 0113
    NF C 79-130
    NF C 63-650
    EN/IEC 60947-2
    EN/IEC 60947-1
    product certifications
    UL
    DNV
    protective treatment
    TC
    IP degree of protection
    IP405 with terminal shrouds conforming to IEC 60529
    pollution degree
    3
    ambient air temperature for operation
    -13...158 °F (-25...70 °C)
    ambient air temperature for storage
    -67...203 °F (-55...95 °C)
    fire resistance
    1760 °F (960 °C) conforming to IEC 60695-2-1
    operating altitude
    6561.68 ft (2000 m)
    Offer Sustainability
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Available
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    Catalog
    Date
    Size
    Add to My Documents
    GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors (Version 1.0)
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    REACh Declaration
    Date
    Size
    Add to My Documents
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.