Choose another country or region

Schneider Eletric

Range: TeSys D

Contactors

LC1D80B7

Schneider Eletric
Range: TeSys D

Contactors

LC1D80B7

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A - 24 V AC 50/60 Hz coil

Show more characteristics >
Buy online
No online offers found
Add to My Products Remove from My Products

  • Main
    range
    TeSys
    product name
    TeSys D
    product or component type
    Contactor
    device short name
    LC1D
    contactor application
    Motor control
    Resistive load
    utilisation category
    AC-1
    AC-3
    AC-4
    poles description
    3P
    power pole contact composition
    3 NO
    System Voltage
    <= 690 V AC power circuit
    <= 300 V DC 25...400 Hz power circuit
    [Ie] rated operational current
    125 A (<= 140 °F (60 °C)) at <= 440 V AC AC-1 power circuit
    80 A (<= 140 °F (60 °C)) at <= 440 V AC AC-3 power circuit
    motor power kW
    22 kW at 220...230 V AC 50/60 Hz AC-3
    37 kW at 380...400 V AC 50/60 Hz AC-3
    45 kW at 660...690 V AC 50/60 Hz AC-3
    45 kW at 415...440 V AC 50/60 Hz AC-3
    55 kW at 500 V AC 50/60 Hz AC-3
    45 kW at 1000 V AC 50/60 Hz AC-3
    15 kW at 400 V AC 50/60 Hz AC-4
    motor power HP (UL / CSA)
    20 hp at 200/208 V AC 50/60 Hz 3 phases motors
    7.5 hp at 115 V AC 50/60 Hz 1 phase motors
    15 hp at 230/240 V AC 50/60 Hz 1 phase motors
    25 hp at 230/240 V AC 50/60 Hz 3 phases motors
    60 hp at 460/480 V AC 50/60 Hz 3 phases motors
    60 hp at 575/600 V AC 50/60 Hz 3 phases motors
    control circuit type
    AC 50/60 Hz
    [Uc] control circuit voltage
    24 V AC 50/60 Hz
    auxiliary contact composition
    1 NO + 1 NC
    [Uimp] rated impulse withstand voltage
    Conforming to IEC 60947
    overvoltage category
    III
    [Ith] conventional free air thermal current
    125 A at <= 140 °F (60 °C) power circuit
    10 A at <= 140 °F (60 °C) signalling circuit
    Irms rated making capacity
    1100 A at 440 V power circuit conforming to IEC 60947
    140 A AC signalling circuit conforming to IEC 60947-5-1
    250 A DC signalling circuit conforming to IEC 60947-5-1
    rated breaking capacity
    1100 A at 440 V power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current
    135 A <= 104 °F (40 °C) 10 min power circuit
    100 A 1 s signalling circuit
    120 A 500 ms signalling circuit
    140 A 100 ms signalling circuit
    640 A <= 104 °F (40 °C) 10 s power circuit
    990 A <= 104 °F (40 °C) 1 s power circuit
    320 A <= 104 °F (40 °C) 1 min power circuit
    associated fuse rating
    160 A gG at <= 690 V coordination type 2 power circuit
    200 A gG at <= 690 V coordination type 1 power circuit
    10 A gG signalling circuit conforming to IEC 60947-5-1
    average impedance
    0.8 mOhm at 50 Hz - Ith 125 A power circuit
    [Ui] rated insulation voltage
    1000 V power circuit conforming to IEC 60947-4-1
    600 V power circuit certifications CSA
    600 V power circuit certifications UL
    690 V signalling circuit conforming to IEC 60947-1
    600 V signalling circuit certifications CSA
    600 V signalling circuit certifications UL
    electrical durability
    0.8 Mcycles 125 A AC-1 at Ue <= 440 V
    1.5 Mcycles 80 A AC-3 at Ue <= 440 V
    power dissipation per pole
    5.1 W AC-3
    12.5 W AC-1
    safety cover
    With
    mounting support
    Plate
    Rail
    standards
    CSA C22.2 No 14
    EN 60947-4-1
    EN 60947-5-1
    IEC 60947-4-1
    IEC 60947-5-1
    UL 508
    product certifications
    BV
    CCC
    CSA
    DNV
    GL
    GOST
    LROS (Lloyds register of shipping)
    RINA
    UL
    connections - terminals
    Control circuit: screw clamp terminals 2 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
    Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: flexible - without cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
    Control circuit: screw clamp terminals 2 cable(s) 0...0.01 in² (1...4 mm²) - cable stiffness: solid - without cable end
    Control circuit: screw clamp terminals 1 cable(s) 0...0 in² (1...2.5 mm²) - cable stiffness: flexible - with cable end
    Power circuit: connector 1 cable(s) 0.01...0.08 in² (4...50 mm²) - cable stiffness: flexible - without cable end
    Power circuit: connector 2 cable(s) 0.01...0.04 in² (4...25 mm²) - cable stiffness: flexible - without cable end
    Power circuit: connector 1 cable(s) 0.01...0.08 in² (4...50 mm²) - cable stiffness: flexible - with cable end
    Power circuit: connector 2 cable(s) 0.01...0.02 in² (4...16 mm²) - cable stiffness: flexible - with cable end
    Power circuit: connector 1 cable(s) 0.01...0.08 in² (4...50 mm²) - cable stiffness: solid - without cable end
    Power circuit: connector 2 cable(s) 0.01...0.04 in² (4...25 mm²) - cable stiffness: solid - without cable end
    tightening torque
    Power circuit: 79.65 lbf.in (9 N.m) - on connector - with screwdriver flat Ø 6 to Ø 8 mm
    Power circuit: 79.65 lbf.in (9 N.m) - on connector hexagonal 0.16 in (4 mm)
    Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Control circuit: 10.62 lbf.in (1.2 N.m) - on screw clamp terminals - with screwdriver Philips No 2
    operating time
    20...35 ms closing
    6...20 ms opening
    safety reliability level
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    mechanical durability
    4 Mcycles
    operating rate
    3600 cyc/h at <= 140 °F (60 °C)
    Complementary
    coil technology
    Without built-in suppressor module
    control circuit voltage limits
    0.85...1.1 Uc operational at 131 °F (55 °C), AC 60 Hz
    0.3...0.6 Uc drop-out at 131 °F (55 °C), AC 50/60 Hz
    0.8...1.1 Uc operational at 55 °C, AC 50 Hz
    inrush power in VA
    245 VA at 68 °F (20 °C) (cos ϕ 0.75) 60 Hz
    245 VA at 68 °F (20 °C) (cos ϕ 0.75) 50 Hz
    hold-in power consumption in VA
    26 VA at 68 °F (20 °C) (cos ϕ 0.3) 60 Hz
    26 VA at 68 °F (20 °C) (cos ϕ 0.3) 50 Hz
    heat dissipation
    6...10 W at 50/60 Hz
    auxiliary contacts type
    Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
    Type mirror contact (1 NC) conforming to IEC 60947-4-1
    signalling circuit frequency
    25...400 Hz
    minimum switching current
    5 mA signalling circuit
    minimum switching voltage
    17 V signalling circuit
    non-overlap time
    1.5 ms on de-energisation (between NC and NO contact)
    1.5 ms on energisation (between NC and NO contact)
    insulation resistance
    > 10 MOhm signalling circuit
    Environment
    IP degree of protection
    IP20 front face conforming to IEC 60529
    protective treatment
    TH conforming to IEC 60068-2-30
    pollution degree
    3
    ambient air temperature for operation
    23...140 °F (-5...60 °C)
    ambient air temperature for storage
    -76...176 °F (-60...80 °C)
    permissible ambient air temperature around the device
    -40...158 °F (-40...70 °C) at Uc
    operating altitude
    9842.52 ft (3000 m) without derating in temperature
    fire resistance
    1562 °F (850 °C) conforming to IEC 60695-2-1
    flame retardance
    V1 conforming to UL 94
    mechanical robustness
    Vibrations contactor open 2 Gn, 5...300 Hz
    Shocks contactor open 8 Gn for 11 ms
    Vibrations contactor closed 3 Gn, 5...300 Hz
    Shocks contactor closed 10 Gn for 11 ms
    height
    5 in (127 mm)
    width
    3.35 in (85 mm)
    depth
    5.12 in (130 mm)
    product weight
    3.51 lb(US) (1.59 kg)
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Need no specific recycling operations
    Contractual warranty
    Warranty period
    18 months
  • Documents and Downloads

    Language
    • English
    • Spanish
    Data Bulletin
    Date
    Size
    Add to My Documents
    Date 09/03/18
    Size 1.5 MB
    CAD
    Date
    Size
    Add to My Documents
    IEC Contactor, 80A, 3 Pole, D-Line (TESYS)
    Certificate
    Date
    Size
    Add to My Documents
    Date 10/11/17
    Size 510.7 KB
    Date 08/02/18
    Size 1.9 MB
    Instruction Sheet
    Date
    Size
    Add to My Documents
    Date 14/07/18
    Size 164.6 KB
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 20/07/18
    Size 289.1 KB
    Product Environmental Profile
    Date
    Size
    Add to My Documents
    Date 18/09/17
    Size 194.5 KB
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Success Stories

    Transtherm Case Study

    Schneider Electric interviewed Transtherm director Tim Bound about our work together. The industry of tomorrow will be different. More volatile markets, new technology capabilities, increased pressure on performance.

    A Tour of Schneider Electric's Modicon M580 ePAC

    Dave Sutton of Schneider Electric gives a guided tour of the features, architecture and benefits of the company's revolutionary ethernet Programmable Automation Controller - ePAC. Learn more on Modicon M580
  • Dimensions Drawings

    Dimensions


    (1)
    Minimum electrical clearance

    LC1

    D80

    D95

    a

    85

    85

    b1

    with LA4 D●2

    135

    135

    with LA4 DB3 or LAD 4BB3

    135

    with LA4 DF, DT

    142

    142

    with LA4 DM, DW, DL

    150

    150

    c

    without cover or add-on blocks

    125

    125

    with cover, without add-on blocks

    130

    130

    c1

    with LAD N (1 contact)

    150

    150

    with LAD N or C (2 or 4 contacts)

    158

    158

    c2

    with LA6 DK10, LAD 6DK

    170

    170

    c3

    with LAD T, R, S

    178

    178

    with LAD T, R, S and sealing cover

    182

    182


  • Connections and Schema